<link rel="stylesheet" href="styles.f3b1fba60ec7970c.css">
Documento de conferencia
Access status: Open Access ,

Evaluación y comparación de algoritmos de clasificación de eventos de tensión mediante su implementación en un DSP

Abstract

This paper assesses the experimental implementation of three voltage events classification algorithms. They are known in the literature as symmetrical component algorithm, six-phase algorithm and space vector algorithm. They use the fundamental voltages and sequence’s components estimated by a sequence detector proposed by the authors previously. This detector is synchronized with the network achieving phase and frequency adaptation and high rejection to the network disturbances. From implementation of classification algorithm and detector on a DSP (Digital Signal Processor), the performance of each algorithm in the classification of real events and their possible application in a PQM (Power Quality Monitor) was evaluated.

Keywords
events classification
signal processing algorithms
digital signal processing
discrete fourier transforms
http://creativecommons.org/licenses/by-nc-sa/4.0/

This work is published under license Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International (BY-NC-SA 4.0)

item.page.license
Loading...
Thumbnail Image